[sheepishly]

I did the exact same thing only to discover that the power supplies on the units that blew weren't auto-switching and the rack and UPS were delivering 220. It took two power supplies for me to get the message.....

Pete Helgren
Value Added Software, Inc
www.asaap.com
www.opensource4i.com


On 2/19/2011 8:06 AM, Jim Franz wrote:
Have a customer switching their standalone ups to a IBM (Eaton) rack ups-same kVa, and when they plugged in a power cable from phone closet that had internet router it blew the power supply in the router. 2 other older pc's blew power supplies.
But the i and rest of servers/switches came up fine. I'm remote& can't see what's going on. Any ideas i can point them to? I've recommended they call svc on the UPS.
Jim Franz

As an Amazon Associate we earn from qualifying purchases.

This thread ...

Follow-Ups:
Replies:

Follow On AppleNews
Return to Archive home page | Return to MIDRANGE.COM home page

This mailing list archive is Copyright 1997-2024 by midrange.com and David Gibbs as a compilation work. Use of the archive is restricted to research of a business or technical nature. Any other uses are prohibited. Full details are available on our policy page. If you have questions about this, please contact [javascript protected email address].